 Industrial Power Supplies
TIS Series
Features
Switch mode power supplies for DIN-rail mounting 4 power ranges with 3, 6, 12 and 24 A output current (24 VDC models) Selectable 115/ 230 VAC input Very low ripple and noise EMI complies with EN50081-2 and EN50082-2 Conducted EMI to EN55011 class B For system operation available with built-in functions: RED: Redundancy module for N+1 systems with true current sharing. SIG: Signal module with AC-Powerfail, DC- OK Signal and The switching power supplies of the TIS series have been particulary deexternal ON/OFF control signed for applications in industrial process control systems and machine tools. Excellent specifications and high immunity against electrical disturUDS: DC-UPS module for uninterbances guarantee reliable power for sensitive loads in rugged industrial ruptable battery backed-up environments. With help of optional function modules specific requirements power systems. for system applications can be met by a standard product. With the UDS Worldwide Safety Approvals module the power supplies can be extended to a perfect DC-UPS with autoEasy snap-on mounting on DIN-rails matic battery- backup. This function is very often required in applications or chassis mounting where a time delayed shutdown of a system is necessary. To monitor and 2 Year Product Warranty control the power supply a signal module can be installed. For parallel operation with active power sharing a redundancy option is available. This flexibility makes the TIS series power supplies a cost effective solution for many industrial applications.
75 - 600 Watt
Models
Ordercode (includes terminal plugs) TIS 75-112 TIS 75-124 TIS 75-148 TIS 150-124 TIS 150-148 TIS 300-124 TIS 300-148 TIS 300-172 TIS 500-124 TIS 600-124 TIS 600-128 TIS 600-148 TIS 600-172 TIS 300-124 DCI Input Voltage Output Power max. Output Voltage nom. 12 VDC 24 VDC 48 VDC 24 VDC 48 VDC 24 VDC 48 VDC 72 VDC 24 VDC 24 28 48 72 VDC VDC VDC VDC Output Current max. 6.0 A 3.0 A 1.5 A 6.0 A 3.0 A 12 A 6.0 A 4.2 A 20 A 24 A 22 A 12 A 8.5 A 12 A
115 / 230 VAC selectable 115 / 230 VAC selectable 115 / 230 VAC selectable 230 VAC 115 / 230 VAC selectable 300 - 800 VDC
75 W
150 W
300 W 500 W
600 W
300 W
24 VDC
http://www.tracopower.com
Page 1
Industrial Power Supplies
TIS Series 75-600 Watt
Input Specifications
Input voltage range - TIS 75, TIS 150, TIS 300, TIS 600 - TIS 500 - TIS 300 DCI Input frequency Input current at full load (typ.) - TIS 75 - TIS 150 - TIS 300 - TIS 500 - TIS 600 Inrush current (< 2 ms) - TIS 75 - TIS 150 - TIS 300 - TIS 500 - TIS 600 93 - 132 VAC / 187 - 264 VAC 187 - 264 VAC 300 - 800 VDC 47 - 63 Hz 115 VAC 1.7 A 3.0 A 5.4 A 10.5 A 115 VAC < 16.5 A < 35 A < 35 A < 70 A 230 VAC 0.9 A 1.7 A 3.3 A 5.5 A 6.4 A 230 VAC < 33 A < 70 A < 70 A < 70 A < 80 A
Output Specifications
Output voltage adj. range - - - - - 12 24 28 48 72 VDC VDC VDC VDC VDC models models models models models - TIS 75, TIS 150 - TIS 300, TIS 500, TIS 600 12 24 28 48 60 - - - - - 14 28 32 52 76 VDC VDC VDC VDC (48 - 55 VDC on request)) VDC
Regulation - Input variation - Load variation (10 - 90 %)
0.2 % max. 1.0 % max. 0.3 % max. ( 1.5 % in parallel operation) < 50 mV pk-pk current limitation at 110 % typ. (constant current, automatic restart) 140 % typ. Vout nom. 115 VAC min. 25 ms min. 15 ms 230 VAC min. 30 ms min. 40 ms min. 25 ms
Ripple and Noise (20MHz Bandwidth) Electronic short circuit protection Overvoltage protection, triggerpoint at Hold-up time - TIS 75 ... TIS 300 - TIS 500 - TIS 600
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated. http://www.tracopower.com Page 2
Industrial Power Supplies
TIS Series 75-600 Watt
General Specifications
Temperature ranges - Operating (ambient temp.) - Derating above 50 C - Storage (non operating) Humidity (non condensing) Temperature coefficient Switching frequency Efficiency - TIS 75 ... TIS 300 - TIS 500 - TIS 600 Isolation Reliability, calculated MTBF (MIL-HDBK-217 E) - TIS 75 /150 - TIS 300 /500 - TIS 600 Safety standards Safety approvals - 25 C...+70 C max. 2% /C - 25 C...+ 85 C 95 % rel H max. 0.02 % / C 80 kHz typ. (Pulswidth modulation) 85 % typ. 90 % typ. 88 % typ. according to EN 60950, UL 1950, UL 508C 450000 h @ +25C/ 420000 h @ +25C 360000 h @ +25C/ 340000 h @ +25C 300000 h @ +25C IEC 60950, EN 60950 (SELV), UL/cUL 1950, UL 508C UL/cUL 1950 recognized, File E18138 UL/cUL 508C listed, File E210002 UL/cuL 1604 listed, File E213613 (Class I,Division 2, Groups A, B, C and D hazardous locations) CB-Scheme EN 50081-1 / EN 50081-2 EN 55011 class B, EN 55022 class B, FCC part 15, level B EN 55011 class A, EN 55022 class A, FCC part 15, level A EN 50082-2 IEC / EN 61000-4-2 IEC / EN 61000-4-3 IEC / EN 61000-4-4 IEC / EN 61000-4-5 IEC / EN 61000-4-6 IEC / EN 61000-4-8 IP 20 (IEC 529) - Vibration - Shock IEC 60068-2-6,1 gn, 200 sweeps, each axis IEC 60068-2-27, 15 gn, 11 ms, each axis Aluminium (chassis) / stainless steel (cover) for 35 mm DIN-rails as per EN 50022 Plugable screw terminals (plugs included) (TIS 600: screw terminal blocks) Page 3 4 kV / 8 kV 10 V / m 2 kV 2 kV / 4 kV 10 V 30 A / m
Electromagnetic compatibility (EMC), Emissions - Conducted RI suppression on input - Radiated RI suppression Electromagnetic compatibility (EMC), Immunity - Electrostatic discharge (ESD) - Radiated RF field immunity - Electrical fast transient / burst immunity - Surge immunity - Immunity to conducted RF disturbances - Power frequency field immunity Safety class Case protection Environment Enclosure material Mounting (snap-on with selflocking spring) Connection
Degree of Protection 1 (IEC 536)
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated. http://www.tracopower.com
Industrial Power Supplies
TIS Series 75-600 Watt
Power Supplies with Redundancy Function Optional Mounting Systems Dimensions mm (inches)
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure. This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other options is not possible.
Models
Ordercode (includes terminal plugs) TIS 150-124 RED TIS 150-148 RED TIS 300-124 RED TIS 300-148 RED TIS 600-124 RED TIS 600-148 RED Input Voltage Output Power max. 150 W 300 W 600 W Output Voltage nom. 24 VDC 18 VDC 24 VDC 48 VDC 24 VDC 48 VDC Output Current max. 6.0 A 12 A 12 A 6.0 A 24 A 12 A
115 / 230 VAC selectable 115 / 230 VAC selectable 115 / 230 VAC selectable
115/230VAC
N
Con1 Pin2
Bus Indicator
DC
Con2 - Pin1/2
-Vout
Con1 Pin1 I-Sense V-Sense Con3 - Pin4
Current Shareline
Con3 - Pin3 Con3 - Pin2
Regulator Unit OK
Con3 - Pin1
Unit OK Common Unit OK
Specifications
Raiting per relay contact 60 VDC /0.36 A max.
Specifications can be changed without notice http://www.tracopower.com Page 4
24/48VDC
L
Con1 Pin3
Con2 - Pin3/4
AC
+Vout
Industrial Power Supplies
TIS Series 75-600 Watt
Power Supplies with Powerfail Functions
These models provide 3 functions required in many process control system applications: * AC-Powerfail signal (relay contact) * DC-OK signal (relay contact) * Remote ON/OFF
Models
Ordercode (includes terminal plugs) TIS 150-124 SIG TIS 150-148 SIG TIS 300-124 SIG TIS 300-148 SIG TIS 600-124 SIG TIS 600-148 SIG Input Voltage Output Power max. 150 W 300 W 600 W Output Voltage nom. 24 VDC 48 VDC 24 VDC 48 VDC 24 VDC 48 VDC Output Current max. 6.0 A 3.0 A 12 A 6.0 A 24 A 12 A
115 / 230 VAC selectable 115 / 230 VAC selectable 115 / 230 VAC selectable
115/230VAC
N
Con1 Pin2
Output OK
DC
Con2 - Pin1/2
-Vout
+ -
Remote ON/OFF
Con3 - Pin1
Con3 - Pin7 Con3 - Pin6
Common AC-Powerfail
Mains Fail Detection (Relay A)
Mains OK
Con3 - Pin5 Con3 - Pin4 Con3 - Pin3
DC-OK Common DC-OK
DC-OK Detection (Relay B)
DC-OK
Specifications
DC-OK signal trigger point - Models with 24 Vout - Models with 48 Vout AC-Powerfail signal Raiting per relay contact > 22.8 VDC 0.5 V > 45.6 VDC 1.0 V relay B closed (pin 4 - pin 3) relay B closed (pin 4 - pin 3)
Vin < 93 resp. < 187 VAC relay A closed (pin 7 - pin 6) 60 VDC /0.36 A max.
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated. http://www.tracopower.com Page 5
Remote ON/OFF
Con1 Pin1
Con3 - Pin2
24/48VDC
L
Con1 Pin3
Con2 - Pin3/4
AC
+Vout
Industrial Power Supplies
TIS Series 75-600 Watt
DC-UPS-System
In addition to the standard power supply function, these models include a professional battery management system to charge and monitor an external battery. In case of a power failure the battery is switched automatically and without any interruption to the DC-output. If mains power is available again, the battery is switched off. The hold-up time is limited only by battery capacity and load. Charge current and voltage can be adjusted to values as required by battery type. Power fail and low battery alarm signals
are available via two independent relay contacts. During normal operation the battery status is monitored by periodically loading the battery for short time. If a cell resistance is high, there is a relay alarm available. The battery is fully protected under any operational conditions. The power supply is short circuit protected even in batterybackup operation, however for safety reason the battery should be fused with a fast blow fuse. Battery mode can be activated by connection of Pin 7 and 8.
Complete external battery modules (3.2 Ah or 7 Ah standard) with lead batteries are available on request.
Models
Ordercode (includes terminal plugs) TIS 300-124 UDS TIS 600-124 UDS Input Voltage Output Power max. 300 W 600 W Output Voltage nom. 24 VDC 24 VDC Output Current max. 12 A 24 A
115 / 230 VAC selectable 115 / 230 VAC selectable
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated. http://www.tracopower.com Page 6
Industrial Power Supplies
TIS Series 75-600 Watt
DC-UPS-System
Battery +
Con3 - Pin2
V Battery Charger
Battery -
Con3 - Pin1 I
115/230VAC
L
Con1 Pin3
N
Con1 Pin2
Output OK
DC
Con2 - Pin1/2
-Vout
Con1 Pin1
VBat>18V Bat ON/OFF Mains Fail
Battery Switch Logic
Con4 Pin8 Con4 - Pin3
Battery ON/OFF
Con4 - Pin2 Con4 - Pin1
AC-Powerfail Common AC-Power OK
Con4 Pin7
Mains Fail Detection (Relay A)
AC-Powerfail
Con4 - Pin6 Con4 - Pin5 Con4 - Pin4
Battery Low / failure Common Battery OK
Battery Test (Relay B)
Low Battery
Specifications
Charging current (factory set) - TIS 300-124 UDS - TIS 600-124 UDS 1.2 A 2.4 A 0.15...1.5 A 0.25...2.5 A < 50 mA system switches off relay A closed (pin 2 - pin 3) relay B closed (pin 5 - pin 6) 60 VDC /0.36 A max. output current reduction by 1.4 x battery charge current
Adjustment range of charging current - TIS 300-124 UDS - TIS 600-124 UDS Holding current for charging battery atvoltage 27.3 VDC Overload at short circuit during battery operation AC-Powerfail signal Low battery signal Raiting per relay contact During battery charge operation Vin < 93 resp. < 187 VAC Battery voltage below 22 V
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated. http://www.tracopower.com Page 7
24VDC
AC
Con2 - Pin3/4
+Vout
Industrial Power Supplies
TIS Series 75-600 Watt
Battery-Pack for DC-UPS Systems
The Battery Pack contains high quality, maintenance free lead-acid batteries with 3.2 Ah resp. 7.0 Ah capacity. The batteries are fixed together with a re-settable electronic fuse on a solid mounting frame. Together with power supply models TIS 300-124 UDS or TIS 600-124 UDS the battery pack provides a complete and reliable DC-UPS system. Backup time is depending on load current and battery capacity.
Models
Ordercode Battery Voltage Battery Capacity (25C, 20h-rate) 3.2 Ah 7.0 Ah Permissable Charge Current max. 1.2 A 2.4 A
TIS 24-32 AP TIS 24-70 AP
24 VDC 24 VDC
Specifications
Max. charge voltage Temperature coefficient Temperature range - at charge operation - at load operation - Storage 27...27.6 VDC - 36mV /C - 15 C...+50 C - 20 C...+60 C - 20 C...+60 C 4...5 years 1.0 m - TIS 24-32 AP - TIS 24-70 AP - TIS 24-32 AP - TIS 24-70 AP 2.5 mm2 (AWG 12) 4.0 mm2 (AWG 11) 4.6 kg (10.1 lb) 5.9 kg (13.0 lb) TIS 300-124 UDS TIS 600-124 UDS
Average lifetime on standby operation at tA =20 C Cable length Cable diameter Weight
Recommended combinations - TIS 24-32 AP (power supplies) - TIS 24-70 AP
All specifications valid at nominal input voltage, full load and +25C after warm-up time unless otherwise stated. http://www.tracopower.com Page 8
Industrial Power Supplies
TIS Series 75-600 Watt
Optional Mounting Systems Dimensions mm (inches) TIS 75
LN
TIS 150
+-
OUTPUT
adj
114.6 (4.51)
Industrial Switching Power Supply TIS-75-124 24VDC / 3 A
Nom. Freq.: 50/60 Hz Nom. Voltage: 115/230 VAC Nom. Current: 1,7/0,9 A
114.6 (4.51)
INPUT
+-
Industrial Switching Power Supply TIS150-124 24VDC / 6 A
Output
Nom. Voltage: 24 VDC Nom. Current: 6 A
Output O
K
Nom. Voltage: 24 VDC Nom. Current: 3 A
Output
Output O K
CAUTION
Input
Nom. Freq.: 50/60 Hz Nom. Voltage: 115/230 VAC Nom. Current: 3,7/1,7 A
(2.11)
53.7
NL
Check line selection switch before connection.
90 (3.54) 45 (1.77)
56.7 (2.23)
(2.11)
53.7
Do not open. Risk of high voltage. Read instruction manual. Check line selection switch before connection.
CAUTION
Do not open. Risk of high voltage. Read instruction manual.
157 (6.18) 38.5
(1.52)
56.7 (2.23)
80 (3.15)
56.7 (2.23)
56.7 (2.23)
(0.27)
Weight: TIS 75 0.48 kg (1.06 lb) TIS 150 0.80 kg (1.76 lb)
TIS 300
++ - -
114.6 (4.51)
Industrial Switching Power Supply TIS 300-124 24VDC / 12A
Output
Nom. Voltage: 24 VDC Nom. Current: 12 A
Output O
K
Input
Nom. Freq.: 50/60 Hz Nom. Voltage: 115/230 VAC Nom. Current: 5,4/3,3 A
CAUTION
NL
Check line selection switch before connection.
207 (8.15) 38.5
(1.52) (0.27)
(2.11)
53.7
Do not open. Risk of high voltage. Read instruction manual.
83 (3.27)
130 (5.12)
83 (3.27)
6.8
Weight: TIS 300 1.4 kg (3.09 lb)
Specifications can be changed without notice http://www.tracopower.com
Tolerances: 0.5 mm (0.02) Page 9
(0.27)
6.8
6.8
Industrial Power Supplies
TIS Series 75-600 Watt
Optional Mounting Systems Dimensions mm (inches) TIS 500
CAUTION
130 (5.12)
Industrial Switching Power Supply TIS 500-124 24VDC / 20A NL
Do not open. Risk of high voltage. Read instruction manual.
++ - -
Output
Nom. Voltage: 24VDC Nom. Current: 20 A
Input
Nom. Freq.: 50/60 Hz Nom. Voltage: 230 VAC Nom. Current: 5,3 A
75 (2.95)
220 (8.66) 46 (1.81) 130 (5.12)
83 (3.27)
Weight:
(0.27)
TIS 600
NL
Nom. Freq.: 50/60 Hz Nom. Voltage: 115/230 VAC Nom. Current: 10,5/6,4 A
83 (3.27)
- - ++
Output
Nom. Voltage: 72 VDC Nom. Current: 8 A
177.2 (6.98)
Industrial Switching Power Supply TIS 600-124 24VDC / 24A
Input
CAUTION
243 (9.57) 32
(1.26)
120.2 (4.73)
Do not open. Risk of high voltage. Read instruction manual. Check line selection switch before connection.
6.8
TIS 500
1.9 kg (4.19 lb)
82.6 (3.25)
179 (7.05)
Weight:
82.8 (3.26)
(0.27)
6.8
TIS 600
2.0 kg (4.41 lb)
Specifications can be changed without notice http://www.tracopower.com
Tolerances: 0.5 mm (0.02) Page 10
Industrial Power Supplies
TIS Series 75-600 Watt
Optional Mounting Systems Dimensions mm (inches) Wall mounting
A B C 7.5
(0.30)
D
4.6
(0.18)
Models
TIS 75W TIS 150W TIS 300W TIS 500W TIS 600W
Order code
MK-75 MK-150 MK-300 MK-500 MK-600
A
37 (1.46) 132 (5.20) 132 (5.20) 132 (5.20) 190 (7.48)
E
B
14.5 (0.57) 13.5 (0.53) 13.5 (0.53) 13.5 (0.53) 37.5 (1.48)
C
- 105 (4.13) 105 (4.13) 105 (4.13) 115 (4.53)
D
134.5 (5.30) 134.5 (5.30) 134.5 (5.30) 134.5 (5.30) 197.0 (7.76)
E
150.5 (5.93) 150.5 (5.93) 150.5 (5.93) 150.5 (5.93) 207.0 (8.15)
Rugged DIN-Rail mounting
B C
A
4.2 (0.17)
50.1 (1.97)
countersink M4
25 (0.98)
Models
TIS 150W TIS 300W TIS 500W TIS 600W
Order code
RMK-150 RMK-300 RMK-500 standard
A
t.b.a. t.b.a. t.b.a. 180 (7.09)
B
t.b.a. t.b.a. t.b.a. 165 (6.50)
C
t.b.a. t.b.a. t.b.a. 15.0 (0.59)
Specifications can be changed without notice http://www.tracopower.com
Tolerances: 0.5 mm (0.02) Page 11
Industrial Power Supplies
TIS Series 75-600 Watt
Outline Dimensions mm (inches) TIS-24-32 AP
204 (8.03) 184 (7.24)
14
(0.55)
7
(0.28)
Detail A
A
A
(0.23)
5.8
100 (3.94)
135 (5.14)
B
B
7
(0.28)
Detail B
(0.35)
69 (2.72)
Weight (incl. batteries): TIS-24-32 AP TIS-24-70 AP 4.6 kg (10.1 lb) 5.9 kg (13.0 lb)
TIS-24-70 AP
272 (10.71) 252 (9.92)
A
A
100 (3.94)
B
B
Specifications can be changed without notice
69 (2.72)
152 (5.98)
Tolerances: 0.5 mm (0.02)
Rev. 05/01
Jenatschstrasse 1 * CH-8002 Zurich * Switzerland Tel. +41-1284 2911 * Fax +41-1201 1168 * e-mail: sales@traco.ch * internet: http://www.tracopower.com
9
(0.47)
12
Page 12


▲Up To Search▲   

 
Price & Availability of TIS75

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X